Trickling Filter Designer
Design a single-stage trickling filter by the NRC equations. Enter the design flow, the influent (post-primary) BOD and the target effluent BOD, plus the recirculation ratio and filter depth — the app finds the recirculation factor, the required volume, area & diameter, the organic and hydraulic loading rates, and the BOD-removal efficiency achieved.
① Flow & BOD loading
② Recirculation
NRC (SI): E = 100 / (1 + 0.4432·√(W/(V·F))) with recirculation factor F = (1+R)/(1+R/10)², where W = BOD load (kg/day) and V = filter volume (m³).
🦠 Trickling filter design
Worked solution
Sign in to your Ebora account
Sign in to use the Trickling Filter Designer and see your Ebora Points balance.
Top up Ebora Points
1 EP = ₱1 · Minimum top-up 50 EP · Pay via GCash / Maya / Bank QRPh